Bottling Plant CIP Room Ventilation
A bottling plant's clean-in-place room lost all six of its fans to drives locked out on alarms. We traced the faults, reprogrammed the drives and got the room breathing again.
The Challenge
The clean-in-place room at a Northern California bottling plant lost its ventilation. A supply fan, two exhaust fans and three return fans were all down, their variable-speed drives locked out on alarms that would not reset.
A CIP room without airflow fills with heat and chemical vapor, so it was not a problem that could wait.
What We Did
- Traced the lockouts to drives set up to run off the wrong control signals, and corrected the control setup.
- Reprogrammed every drive for the motor it actually runs. None had been set up for the motors installed.
- Pulled filter media that had wrapped around a supply fan's blade and shaft.
- Found a loose power connection causing a phase-loss alarm on an exhaust fan's drive, and tightened it.
The Result
All six fans are running again. The plant's make-up air units and its supply and exhaust fans are now on our preventive maintenance program, so belts, bearings, filters and controls get checked before they fail.
More Food & Beverage Work
See everything we do for food and beverage plants or browse all projects.

Winery Cold Room & Control Rooms
A winery's walk-in cooler had climbed to 49°F while the units cooling its boiler control and motor control rooms failed. We brought all three rooms back to temperature.

Produce Packer Floor Drains
Floor drains across a produce packer's docks, processing areas and coolers were holding water. We cleared them overnight, after production, and put them on a schedule.
Have a Problem Like This?
Tell us what's going on and we'll walk the site and put together a quote. If something is down right now, call the service line.