A winery's walk-in cooler had climbed to 49°F while the units cooling its boiler control and motor control rooms failed. We brought all three rooms back to temperature.

The Challenge

At a Central Valley winery, a walk-in cooler had climbed to 49°F. At the same time, the air conditioning protecting a boiler control room and a motor control room had failed.

Electrical rooms that overheat can trip the equipment the whole plant runs on, and a warm cooler puts product at risk.

What We Did

  1. Cooler: used dye already in the system to find a refrigerant leak at a liquid-line valve, replaced the valve and filters, then evacuated and recharged the system.
  2. Boiler control room: the compressor had burned out from overheating. We replaced it with a new filter drier and contactor, then found and replaced a failed expansion valve that was freezing the coil.
  3. Motor control room: cleaned the plugged coils, kept the unit cooling on one circuit while the parts came in, then replaced the failed compressor.

The Result

The cooler is cycling on temperature again and both control rooms are holding temperature. This winery is one of our busiest service accounts, with more than 80 service calls this year.

  • IndustryWinery
  • LocationCentral Valley, CA
  • ServicesRefrigeration repair, HVAC repair, compressor replacement
  • ResultCold room and control rooms back to temperature